S330M
S330M
Electronic governor
Mechanically welded chassis with antivibration suspension
Main line circuit breaker
Radiator for wiring temperature of 48/50°C max with mechanical fan
Protective grille for fan and rotating parts
9 dB(A) silencer supplied separately
Charger DC starting battery with electrolyte
24 V charge alternator and starter
Delivered with oil and coolant -30°C
Manual for use and installation
SPECIFICATIONS
S330M
Engine Model
Alternator type
Performance class
DC09 072A
ECO38-2L4A
G2
DIMENSIONS COMPACT VERSION
Length (mm)
Width (mm)
Height (mm)
Dry weight (kg)
Tank capacity (L)
3000
1100
1492
1850
340
GENERAL CHARACTERISTICS
Frequency (Hz)
Reference voltage (V)
Max power ESP (kVA)
Max power ESP (kWe)
Max power PRP (kVA)
Max power PRP (kWe)
Intensity (A)
Standard Control Panel
Optional control panel
50
400/230
330
264
300
240
433
DSE 4510
DSE 6610
POWER
Voltage
415/240
400/230
380/220
kWe ESP
264
264
264
kVa ESP
330
330
330
kWe PRP
240
240
240
kVa PRP
300
300
300
Standby Amps
459
476
501
ENGINE SPECIFICATIONS
GENERAL ENGINE DATA
Engine model
Cylinder arrangement
Displacement (C.I.)
Bore (mm) x Stroke (mm)
Compression ratio
Speed (RPM)
Pistons speed (m/s)
Maximum stand-by power at rated RPM (kW)
Frequency regulation (%)
BMEP (bar)
Governor type
SCANIA DC9 072A 4-temps, Turbo , Air/Air DC 5 X
L
9.3
130 x 140
16.1
1500
7.0
273
+/- 0.5%
23.47
Electronic
COOLING SYSTEMS
Radiator & Engine capacity (L)
Max water temperature (°C)
Outlet water temperature (°C)
Fan power (kW)
Fan air flow w/o restriction (m3/s)
Available restriction on air flow (mm water column)
Type of coolant
Thermostat (°C)
37
95
80
6
6.1
20
SCANIA
80-87
EMISSIONS
Emission PM (g/kW.h)
Emission CO (g/kW.h)
Emission HCNOx (g/kWh)
Emission HC (g/kW.h)
N/A
N/A
N/A
N/A
EXHAUST
Exhaust gas temperature (°C)
Exhaust gas flow (kg/min)
Max. exhaust back pressure (mm water column)
427
23
750
FUEL
Consumption @ 110% load (L/h)
Consumption @ 100% load (L/h)
Consumption @ 75% load (L/h)
Consumption @ 50% load (L/h)
Maximum fuel pump flow (L/h)
N/A
N/A
N/A
N/A
N/A
OIL
Oil capacity (L)
Min. oil pressure (bar)
Max. oil pressure (bar)
Oil consumption 100% load (g/kWH)
Carter oil capacity (L)
31
3
6
<0.2
N/A
HEAT BALANCE
Heat rejection to exhaust (kW)
Radiated heat to ambiant (kW)
Haet rejection to coolant (kW)
165
20
84+52
AIR INTAKE
Max. intake restriction (mm water column)
Intake air flow (kg/min)
625
22